Foam
Chamber is used in one of the most common
application to protect vertical fixed roof (cone)
liquid storage tanks, with or without internal
floating roof with the low expansion foam system.
Foam Chambers are air aspirating devices used for
the protection of fixed roof flammable liquid
storage tanks. This method consists of one or more
foam chambers installed on the shell of the tank
just below the roof joint. A foam solution pipe
extends from the proportioning source outside the
dike wall to the foam maker located upstream of the
chamber. Foam Chambers are widely used with the line
proportioner and bladder tank / balanced pressure
pump in low expansion foam system. Upon entering the
chamber the foam solution is expanded and then
discharged against a deflector mounted inside.
MATERIAL | : | Carbon Steel Construction / Stainless Steel Construction |
NLET SIZE | : | 65, 80, 100 NB |
WORKING PRESSURE | : | 2.8 to 7.0 Bar (40 - 100 PSI) |
VAPOUR SEAL RUPTURE PRESSURE | : | 0.7 to 1.75 Bar (10 - 25 PSI) |
MAXIMUM PWEMISIBLE BACK PRESSURE ON VAPOUR SEAL | : | 0.07 Bar (1.0 PSI) |
VAPOUR SEAL | : | Glass |
DEFLECTOR | : | Solid / Split |
FINISH | : | Red Powder Coated |
APPROVALS | : | UL Listed |